  • 1 courant de référence d'un parafoudre

    1. классификационный ток ОПН

     

    классификационный ток ОПН
    Iкл

    Амплитудное значение (более высокое амплитудное значение из двух полярностей, если ток асимметричен) активной составляющей тока промышленной частоты, которое используется для определения классификационного напряжения ОПН и нормируется изготовителем.
    [ ГОСТ Р 52725-2007]

    EN

    reference current of an arrester
    peak value (the higher peak value of the two polarities if the current is asymmetrical) of the resistive component of a power-frequency current used to determine the reference voltage of the arrester
    NOTE 1 The reference current will be high enough to make the effects of stray capacitances at the measured reference voltage of the arrester units (with designed grading system) negligible and is to be specified by the manufacturer.
    NOTE 2 Depending on the nominal discharge current and/or line discharge class of the arrester, the reference current will be typically in the range of 0,05 mA to 1,0 mA per square centimetre of disc area for single column arresters.
    [IEC 60099-4, ed. 2.0 (2004-05)]

    FR

    courant de référence d'un parafoudre
    valeur de crête (la plus grande des deux polarités si le courant est dissymétrique) de la composante résistive du courant à fréquence industrielle utilisée pour déterminer la tension de référence d'un parafoudre.
    NOTE 1 Il convient que le courant de référence soit suffisamment élevé pour rendre négligeables les effets des capacités parasites aux tensions de référence mesurées sur les éléments de parafoudre (avec leur système de répartition) et qu’il soit spécifié par le constructeur.
    NOTE 2 Fonction du courant de décharge nominal et/ou de la classe de décharge de ligne du parafoudre, il convient que le courant de référence soit typiquement dans la gamme de 0,05 mA à 1,0 mA par centimètre carré de surface de disque pour les parafoudres à colonne unique
    [IEC 60099-4, ed. 2.0 (2004-05)]

    Тематики

    • высоковольтный аппарат, оборудование...

    EN

    FR

    Франко-русский словарь нормативно-технической терминологии > courant de référence d'un parafoudre

  • 2 tension de référence d'un parafoudre

    1. классификационное напряжение ОПН

     

    классификационное напряжение ОПН
    Uкл

    Максимальное (амплитудное) значение напряжения промышленной частоты, деленное на √2, которое должно быть приложено к ОПН для получения классификационного тока. Классификационное напряжение многоэлементного ОПН определяется как сумма классификационных напряжений отдельных элементов.
    [ ГОСТ Р 52725-2007]

    EN

    reference voltage of an arrester, Uref
    peak value of power-frequency voltage divided by √2 which is applied to the arrester to obtain the reference current
    NOTE 1 The reference voltage of a multi-unit arrester is the sum of the reference voltages of the individual units.
    NOTE 2 Measurement of the reference voltage is necessary for the selection of a correct test sample in the operating duty test.
    IEC 60099-4, ed. 2.0 (2004-05)

    FR

    tension de référence d'un parafoudre, Uref
    valeur de crête divisée par √2 de la tension à fréquence industrielle qui est appliquée aux bornes du parafoudre pour que celui-ci soit parcouru par le courant de référence.
    NOTE 1 La tension de référence d'un parafoudre à plusieurs éléments est la somme des tensions de référence des éléments séparés.
    NOTE 2 La mesure de la tension de référence est nécessaire au choix d'un échantillon d'essai convenable dans l'essai de fonctionnement.
    IEC 60099-4, ed. 2.0 (2004-05)

    Тематики

    • высоковольтный аппарат, оборудование...

    EN

    FR

    Франко-русский словарь нормативно-технической терминологии > tension de référence d'un parafoudre

  • 3 tension assignée d'un parafoudre

    1. номинальное напряжение ОПН

     

    номинальное напряжение

    Действующее значение напряжения промышленной частоты, которое ограничитель может выдерживать в течение 10 с в процессе рабочих испытаний. Номинальное напряжение должно быть не менее 1,25 наибольшего длительно допустимого рабочего напряжения.
    [ ГОСТ Р 52725-2007]

    EN

    rated voltage of an arrester
    Ur

    maximum permissible r.m.s. value of power-frequency voltage between its terminals at which it is designed to operate correctly under temporary overvoltage conditions as established in the operating duty tests
    NOTE 1 The rated voltage is used as a reference parameter for the specification of operating characteristics.
    NOTE 2 The rated voltage as defined in this standard is the 10 s power-frequency voltage used in the operating duty test after high-current or long-duration impulses. Tests used to establish the voltage rating in IEC 60099-1, as well as some national standards, involve the application of repetitive impulses at nominal current with power-frequency voltage applied. Attention is drawn to the fact that these two methods used to established rating do not necessarily produce equivalent values (a resolution to this discrepancy is under consideration).
    [IEC 60099-4, ed. 2.0 (2004-05)]

    FR

    tension assignée d'un parafoudre
    Ur

    valeur maximale de la tension efficace à fréquence industrielle admissible entre ses bornes pour laquelle le parafoudre est prévu pour fonctionner correctement dans des conditions de surtension temporaires comme il est défini dans les essais de fonctionnement
    NOTE 1 La tension assignée est utilisée comme paramètre de référence pour la spécification des caractéristiques de fonctionnement.
    NOTE 2 La tension assignée comme définie dans la présente norme est la tension à fréquence industrielle de 10 s, utilisée pour vérifier la stabilité après application des chocs de courant de grande amplitude ou de longue durée lors de l'essai de fonctionnement. Les essais utilisés pour définir la tension assignée dans la CEI 60099-1, ainsi que dans certaines normes nationales, impliquent l'application de chocs répétés au courant nominal pendant que la tension à fréquence industrielle est appliquée. On attire l'attention sur le fait que ces deux méthodes utilisées pour définir les valeurs assignées ne produisent pas nécessairement des valeurs équivalentes (une résolution de cette différence est à l'étude).
    [IEC 60099-4, ed. 2.0 (2004-05)]

    Тематики

    • высоковольтный аппарат, оборудование...

    EN

    FR

    Франко-русский словарь нормативно-технической терминологии > tension assignée d'un parafoudre

  • 4 Uref

    1. классификационное напряжение ОПН

     

    классификационное напряжение ОПН
    Uкл

    Максимальное (амплитудное) значение напряжения промышленной частоты, деленное на √2, которое должно быть приложено к ОПН для получения классификационного тока. Классификационное напряжение многоэлементного ОПН определяется как сумма классификационных напряжений отдельных элементов.
    [ ГОСТ Р 52725-2007]

    EN

    reference voltage of an arrester, Uref
    peak value of power-frequency voltage divided by √2 which is applied to the arrester to obtain the reference current
    NOTE 1 The reference voltage of a multi-unit arrester is the sum of the reference voltages of the individual units.
    NOTE 2 Measurement of the reference voltage is necessary for the selection of a correct test sample in the operating duty test.
    IEC 60099-4, ed. 2.0 (2004-05)

    FR

    tension de référence d'un parafoudre, Uref
    valeur de crête divisée par √2 de la tension à fréquence industrielle qui est appliquée aux bornes du parafoudre pour que celui-ci soit parcouru par le courant de référence.
    NOTE 1 La tension de référence d'un parafoudre à plusieurs éléments est la somme des tensions de référence des éléments séparés.
    NOTE 2 La mesure de la tension de référence est nécessaire au choix d'un échantillon d'essai convenable dans l'essai de fonctionnement.
    IEC 60099-4, ed. 2.0 (2004-05)

    Тематики

    • высоковольтный аппарат, оборудование...

    EN

    FR

    Франко-русский словарь нормативно-технической терминологии > Uref

См. также в других словарях:

  • классификационный ток ОПН — Iкл Амплитудное значение (более высокое амплитудное значение из двух полярностей, если ток асимметричен) активной составляющей тока промышленной частоты, которое используется для определения классификационного напряжения ОПН и нормируется… …   Справочник технического переводчика

  • классификационное напряжение ОПН — Uкл Максимальное (амплитудное) значение напряжения промышленной частоты, деленное на √2, которое должно быть приложено к ОПН для получения классификационного тока. Классификационное напряжение многоэлементного ОПН определяется как сумма… …   Справочник технического переводчика

  • номинальное напряжение ОПН — номинальное напряжение Uн Действующее значение напряжения промышленной частоты, которое ограничитель может выдерживать в течение 10 с в процессе рабочих испытаний. Номинальное напряжение должно быть не менее 1,25 наибольшего длительно допустимого …   Справочник технического переводчика

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»